3 in 1 || No load test|| Load loss Test, short circuit test in Transformer and load losses calculation

Load loss Test or short circuit test in Transformer

Introduction of Transformer load loss

Because of the low power factor and frequently high test currents, measuring load loss on a power transformer needs special attention and precise measuring equipment.
At the rated frequency, the load loss for a pair of windings is measured with voltage applied to one winding’s terminals, the other winding’s terminals short-circuited, and it’s conceivable that additional windings are open-circuited as well.
The supplied current must equal the corresponding rated current. The measurements must be performed immediately to prevent major mistakes from temperature increases.
The square of the ratio of the test current to the rated current must be multiplied by the measured value of load loss.
The figure that results must then be adjusted to reference temperature. Conventionally, it is assumed that all other losses increase inversely with temperature and that ohmic losses vary directly with temperature.
The 3 different two winding combinations on a three-winding transformer are measured. Recalculating the data, losses are assigned to specific windings. Accordingly, total losses for defined loading scenarios involving all of these windings are calculated.
Errors and losses in external circuits should be kept to a minimum. If they are not obviously negligible, correction for measuring transformer errors and for test connection resistance should be performed.

What is the purpose of short circuit test or load loss test?

The transformer short circuit test is used to measure short circuit parameters, including copper losses, equivalent resistance, voltage regulation, and percentage impedance under full load. It is recommended that this test be performed under rated current conditions.

Why are short circuit tests or load loss test performed?

  • To calculate the transformer equivalent resistance and reactance.
  • To measure the copper loss (varying losses) in the transformer.
  • By obtaining the results of the short circuit test, it is possible to assess the transformer’s voltage regulation or percentage impedance z%.

How to Perform a Short Circuit or load loss test Test

 LV side is short-circuited for Load Loss test
LV side is short-circuited for Load Loss test

On the high voltage side, a short circuit test is performed at the rated current with the L.V. side closed-circuited with a copper bus bar. It is done on the H.V. side because rated current may happen there more conveniently as compared to the L.V. side.

connection diagram
connection diagram

Operational Steps of Short Circuit Test or load loss test

  • First of all note down the ambient temperature of your under-test transformer and the temperature should be between 10 to 40 degrees Celsius, according to specification IEC-60076-1.
  • short the Low voltage/ secondary/ Side of the under-test Transformer.
  • Apply Voltage on the High voltage side/ primary side at the rated current. calculate  rated current  from this formula  Current = Power /Voltage x 1.732
  • Note the Power and Voltage from your power Analyzer and convert the losses on 75 C using this formula       MF= (235+75)/(235+Ambint temperature)
Copper Losses Power
Copper Losses Power
  • This power will be equal to your Load losses or copper losses and Voltage will be equal to the impedance voltage at the ambient temperature.

    3 in 1 || Load loss Test, short circuit test in Transformer and load losses calculation
    3 in 1 || Load loss Test, short circuit test in Transformer and load losses calculation

Introduction of the no-load loss

The operational efficiency of a transformer is intimately connected to its no-load losses. These losses keep occurring as long as the transformer is in operation. For an operational economy, it is crucial that there are no load losses. The heating test also takes into consideration no-load losses. When measuring the no-load loss and current of a transformer, one of the windings (usually the HV winding) is left open while the other is given the rated voltage and frequency (50 HZ or 60 HZ) that is being measured.

No load Power
No load Power

The no-load current (Io) and no-load losses (Po) are measured during this test. The frequency and waveform of the applied voltage have a major impact on the observed losses. Because of this, the voltage waveform should be perfectly sinusoidal and at its rating.

No Load Voltage and Current
No Load Voltage and Current

Most of the time, the tests are done with the supply voltage going from 90% to 115% of the transformer’s rated voltage in small steps. This lets the values at the rated voltage be found as well.

How to produce no load losses in Transformer core.

A power transformer’s core will always use energy when it is energized, and this energy will be in the form of heat. This is called “no-lead losses.” Irrespective of whether the transformer is carrying a load or not, these losses will always happen. No-load loss has various components and is dependent on the quality of core manufacturing and the CRGO steel sheet used in the core building.

Interlaminar loss, hysteresis loss, eddy current loss, and extra losses. A quick peek at these components:

Hysteresis Loss.

The size of the hysteresis loop and frequency are both related to hysteresis loss (a characteristic of the power transformer core material and the peak flux density of 1.5 tesla or 1.7 tesla). Hysteresis loss is the term for the heat that is released as the atoms of the core material realign themselves to line up with the magnetic field being applied.

Eddy current loss

Eddy current (EC) loss can be considered to be divided into two parts: the classical EC loss, which is dependent on the thickness of the core and resistance of lamination steel (core), and the non-classical EC (anomalous) loss, which depends on the grain size of the core material (a larger grain size will result in more loss) and magnetic domain movement during the magnetizing cycle. Eddy current loss is proportional to the square of the supply frequency and the square of the maximum flux density. The second causes higher losses than the first and may be greatly minimized by particular processing of the core material.

Transformer Core Sheets
Transformer Core Sheets

Measurement of no load losses.

The frequency should be within plus or minus 0.5% of the rated frequency as measurements will be performed using a power analyzer. Before beginning the test, it might be required to overexcite the system by gradually raising the voltage to 110%,

  •  Holding it there for a short period of time,
  •  Then gradually lowering it to a minimum. 
  • The observed loss will need to be adjusted since the voltage waveform during this test could be affected (these voltage distortions don’t happen while the transformer is performing because the supply system’s impedance is significantly lower than its primary inductance impedance). 
  • Both the voltmeter reading (U’) and the power analyzer reading (U) of the test voltage must be read throughout the test, and the difference between them should be less than 3% (IEC) or less than 5%. (IEEE).

Precautions

  • The testing area should be cordoned off.
  • Flashing warning lights should start when a transformer is under testing.
  • Use insulation gloves when handling the cables.
  • Make sure that the testing person should be at his defined place.
About Engr.Shahid Ali 71 Articles
My self… Good day! I'm glad you're here. I'm Shahid Ali, and I am working in the field of electrical engineering, specifically for a manufacturer of power and distribution transformers. I've got versatile experience working in the testing laboratory for quality control and quality assurance. I have seen both their differences and similarities in every part of operations, from the technical to the quality management. I have more than 10 years of experience with expertise in the QA/QC Department, Electrical Testing, Customer Support, Troubleshooting, Operational Management, Quality Control Lab, and Administration. I am very good at testing, maintaining, installing, or improving electrical systems, equipment, facilities, or products for home, business, or industrial use. About my job; When it comes to testing transformers, I know how to run both internal and external labs. Managing a testing lab is quite difficult. Transformer testing is more complicated than simply issuing a report and calling it a day. To assure quality and testing, there is a procedure that we must follow and keep in mind. In order to assist and direct individuals who may be considering entering this sector and offering transformer testing services, I will share my experiences and lessons learned on this platform. What can you find out on this website? Some of the things that you can learn here are: Transformer Testing Transformer Inspection Transformer faults Tracing Transformer Oil Testing IEC/ISO 17025:2017 Techniques Measurement Uncertainty Calculation, replicate Resting, Retesting, and many more The reason…. I started this website to assist my fellow transformer engineers who are new in the field of testing and who are involved in transformer testing, as well as people from other fields who want to learn about Transformers and their testing. In order to give a clear explanation of transformer testing to everyone, I will provide my experience on testing setups, testing processes, ISO 17025 interpretations, measurements and test equipment reviews, measurement uncertainty computations, and others that may be related here. I'll make an effort to offer the most simple presentations I can. I wish that everyone should be informed and educated in this sector because I think that technical knowledge will be helpful in our daily lives. What’s in it for me? I'll admit that I'm doing this to make a little money (hopefully), but I also thought that by working, I would be able to give back. Also, since I'm still learning, being able to use this website pushes me to work hard, grow, and learn more. There is always more to learn in this area. And for you... If you ever need help with oil testing, CT/PT testing, or switchgear testing, which is my area of expertise, I would be happy to talk to you. Simply leave your comment below, and be sure to check back often since I'll be updating my blog with fresh material that I come across that I think you'll find interesting. Furthermore, I encourage you to participate on my website if anything I write piques your interest. And please feel free to speak up if you have any interesting information to contribute or any opinions on the stuff I've written and posted on my website. Follow me on this journey of providing Tachnical knowledge Connect with me on my LinkedIn page All the best! Tachnical knowledge

1 Comment

7 Trackbacks / Pingbacks

  1. Transformer Oil and Transformer oil Testing - Tachnicalknowledge: Learn Electrical Transformer testing & Transformer Engineering (For Free)
  2. What is a Switchgear: Its Functions, Basic 3 Types, and Working
  3. 6 Best | Resistance Measurement Methods - Tachnicalknowledge: Learn Electrical Transformer testing & Transformer Engineering (For Free)
  4. what is core loss tester and its types - Tachnicalknowledge: Learn Electrical Transformer testing & Transformer Engineering Solutions (For Free)
  5. LV Circuit Breaker Testing: Understanding the Methods and Importance - Tachnicalknowledge: Learn Electrical Transformer testing & Transformer Engineering Solutions (For Free)
  6. Transformer Insulation Resistance Test - Tachnicalknowledge: Learn Electrical Transformer testing & Transformer Engineering Solutions (For Free)
  7. Best || 2 Describe the Core Balance current Transformer

Leave a Reply

Your email address will not be published.


*